Sauna heater breaker size
How much current a sauna heater draws, and what breaker or fuse that usually means. Use it to plan the circuit and to check what an electrician quotes. The heater manual always has the final word.
Current and breaker by heater size
At 240 V, current is power divided by voltage. In the US, fixed electric heating is treated as a continuous load, so the breaker must be at least 125 % of the current (NEC 424.3(B) with 210.20(A)). The table rounds up to the next common two-pole breaker.
| Heater | Current at 240 V | At 125 % | Common breaker | 400 V three-phase, per phase | Typical fuse |
|---|---|---|---|---|---|
| 3.6 kW | 15.0 A | 18.8 A | 20 A | 5.2 A | 3 × 10 A |
| 4.5 kW | 18.8 A | 23.4 A | 25 A | 6.5 A | 3 × 10 A |
| 6 kW | 25.0 A | 31.3 A | 40 A | 8.7 A | 3 × 10 A |
| 8 kW | 33.3 A | 41.7 A | 50 A | 11.5 A | 3 × 16 A |
| 9 kW | 37.5 A | 46.9 A | 50 A | 13.0 A | 3 × 16 A |
| 10.5 kW | 43.8 A | 54.7 A | 60 A | 15.2 A | 3 × 16 A |
| 12 kW | 50.0 A | 62.5 A | 70 A | 17.3 A | 3 × 20 A |
| 15 kW | 62.5 A | 78.1 A | 80 A | 21.7 A | 3 × 25 A |
| 18 kW | 75.0 A | 93.8 A | 100 A | 26.0 A | 3 × 35 A |
Breakers: 15, 20, 25, 30, 40, 50, 60, 70, 80, 90 and 100 A. Some panels also take 35 and 45 A breakers, which can fit a heater more closely. Fuses: common European sizes 10, 16, 20, 25 and 35 A. Wire size depends on the breaker, the cable type and the run, and is given in the heater manual.
Europe and Finland: three-phase
In Finland and much of Europe, sauna heaters above a few kilowatts are normally connected to three phases at 400 V. The current per phase is then about a third of the single-phase current, which is why a 9 kW heater runs happily on 3 × 16 A fuses. Small heaters can also be connected single-phase at 230 V; the manual lists both options when the heater supports them.
Things the electrician will check
- Panel capacity. A 40–60 A circuit is a big addition. Older panels may need a load calculation or an upgrade.
- Control unit or contactor. Larger heaters and heaters with a separate control panel switch the power through a contactor. Check whether your heater needs one before ordering.
- Cable rated for the heat. The last stretch to the heater runs in a hot room and needs cable rated for it, as the manual specifies.
- Dedicated circuit. The heater gets its own circuit. The lights go on a separate one.
Bigger heater, bigger circuit
A larger heater does not cost more to run per session, because it warms the room faster. What it costs is a larger breaker and thicker wire. If your panel is close to its limit, the next size down with a little more warm-up time may be the sensible choice. The calculator shows warm-up time for the recommended size and one size either side.